Machine Model: CIMTR1
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tp < 0.5*Mult*TimeStep then Tp = 0, ElseIf 0.5*Mult*TimeStep < Tp < Mult*TimeStep then Tp = Mult*TimeStep
- If 0.0 < Tpp < 0.5*Mult*TimeStep then Tpp = 0, ElseIf 0.5*Mult*TimeStep < Tpp < Mult*TimeStep then Tpp = Mult*TimeStep
- Xl, Xp, Xpp and Tpp:
- If Xpp > 0 and Tpp > 0 and Xl >= Xpp then Xl := 0.8*Xpp
- If Xl >= Xp then Xl := 0.5*Xp
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Tp | T' - Transient rotor time constant |
| Tpp | T'' – Sub-transient rotor time constant in sec. |
| H | Inertia constant in sec. |
| X | Synchronous reactance |
| Xp | X' – Transient Reactance |
| Xpp | X'' – Sub-transient Reactance |
| Xl | Stator leakage reactance in p.u. |
| E1 | Field voltage value E1 |
| SE1 | Saturation value at E1 |
| E2 | Field voltage value E2 |
| SE2 | Saturation value at E2 |
| Switch | Switch |
| Ra | Stator resistance in p.u. |
States:
1 – Epr
2 – Epi
3 – Ekr
4 – Eki
5 – Speed wr